When.com Web Search

Search results

  1. Results From The WOW.Com Content Network
  2. Polarity (mutual inductance) - Wikipedia

    en.wikipedia.org/wiki/Polarity_(mutual_inductance)

    Transformers are said to have "additive" or "subtractive" polarity based on their physical arrangement of terminals and the polarity of windings connected to the terminals. The convention used for North American transformers is that, facing the high voltage side of the transformer, the H1 terminal is on the observer's right.

  3. Short-circuit test - Wikipedia

    en.wikipedia.org/wiki/Short-circuit_test

    A different form of short-circuit testing is done to assess the mechanical strength of the transformer windings, and their ability to withstand the high forces produced if an energized transformer experiences a short-circuit fault. Currents during such events can be several times the normal rated current.

  4. Vector group - Wikipedia

    en.wikipedia.org/wiki/Vector_group

    Parallel operations: All the transformers should have same phase rotation, vector group, tap setting & polarity of the winding. Ground fault Relay: A Dd transformer does not have neutral. To restrict the ground faults in such systems, we may use a zigzag wound transformer to create a neutral along with the ground fault relay.

  5. Voltage transformer - Wikipedia

    en.wikipedia.org/wiki/Voltage_transformer

    A 120:120 instrument isolation transformer showing two polarity marking conventions. Voltage transformers (VT), also called potential transformers (PT), are a parallel-connected type of instrument transformer. They are designed to present a negligible load to the supply being measured and have an accurate voltage ratio and phase relationship to ...

  6. Sweep frequency response analysis - Wikipedia

    en.wikipedia.org/wiki/Sweep_frequency_response...

    An initial SFRA test is carried out to obtain the signature of the transformer frequency response by injecting various discreet frequencies. This reference is then used for future comparisons. A change in winding position, degradation in the insulation, etc. will result in change in capacitance or inductance thereby affecting the measured curves.

  7. Open-circuit test - Wikipedia

    en.wikipedia.org/wiki/Open-circuit_test

    The open-circuit test, or no-load test, is one of the methods used in electrical engineering to determine the no-load impedance in the excitation branch of a transformer. The no load is represented by the open circuit, which is represented on the right side of the figure as the "hole" or incomplete part of the circuit.

  8. Condition monitoring of transformers - Wikipedia

    en.wikipedia.org/wiki/Condition_monitoring_of...

    Transformers are the most critical assets of electrical transmission and distribution systems, and their failures could cause power outages, personal and environmental hazards, and expensive rerouting or purchase of power from other suppliers. Identifying a transformer which is near failure can allow it to be replaced under controlled ...

  9. Severity factor - Wikipedia

    en.wikipedia.org/wiki/Severity_factor

    The FDSF is calculated at transformer terminals and it is mathematically defined as = ()where ω is the angular frequency, ESD noStd (ω) is the maximum energy spectral density of the input no-standard transient voltage applied at transformer terminals and ESD envol (ω) is the energy spectral density envelope for all standards dielectric tests at terminals.