In this case a fault between one phase and ground would not cause any significant current. Commonly the neutral is grounded (earthed) through a bond between the neutral bar and the earth bar. It is common on larger systems to monitor any current flowing through the neutral-to-earth link and use this as the basis for neutral fault protection.
In single-ended single-phase systems where the Earth and neutral are combined (TN-C, and the part of TN-C-S systems which uses a combined neutral and earth core), if there is a contact problem in the PEN conductor, then all parts of the earthing system beyond the break will rise to the potential of the L conductor.
Hot is any line or neutral conductor (wire or otherwise) connected with an electrical system that has electric potential relative to electrical ground or line to neutral. Ground is a safety conductor with a low impedance path to earth. It is often called the "ground wire," or safety ground. It is either bare or has green insulation. [1]
In recent US practice, which differs considerably from IEC principles and terminology, "bonding" is used more widely as a term for all the aspects of earthing that are not literally connections with the Earth itself ("grounding"); so the connection of protective earth conductors to the supply neutral (since the TN-C-S system is the only ...
This is done in the UK because many buildings are supplied with a TN−C−S earthing system where the neutral and earth conductors are combined. Close to the electricity meter this conductor is divided into two, the earth and the neutral busbar in the consumer unit. If the ground connection to the neutral is lost, all wiring and other objects ...
Strictly speaking, the terms grounding or earthing are meant to refer to an electrical connection to ground/earth. Bonding is the practice of intentionally electrically connecting metallic items not designed to carry electricity. This brings all the bonded items to the same electrical potential as a protection from electrical shock.
Where a circuit includes a neutral or mid-point conductor identified by colour, the colour used shall be blue. In all installations the earth or protective conductor will remain green-and-yellow. 1992--The IEE wiring regulations were adopted by the British Standards Institute as BS 7671. 1992--
[2] Some codes require a bonding jumper to be pulled into non-metallic conduit or in electrical metallic tubing that may be exposed to corrosion or mechanical damage. In North American electrical codes, an important bonding jumper is found in main electrical panels, where the system neutral conductor is connected to earth ground. This must be ...