  2. Sizing wire and circuit breaker for air conditioner

    forums.mikeholt.com/threads/sizing-wire-and-circuit-breaker-for-air...

    As David stated this is incorrect. The conductors are not required to match the size of the OCPD. In this case they're only required to be sized large enough to meet the MCA of 28.2 amps. The 45 amp OCPD has no relation to the conductor size when using the nameplate values.

  3. Sizing wire size for AC Condensors | Information by Electrical...

    forums.mikeholt.com/threads/sizing-wire-size-for-ac-condensors.113883

    I have noticed lately that some condensers have max overcurrent protection size of 25a. Which I install accordingly instead of the 2pole30. Still running the 10/2. I have read on a few different websites that electricians are sizing their wire according to the nameplate rating "minimum circuit ampacity" 2 - 2 1/2 tons 14amps, 18amps...

  4. Sizing a Wire Trough Correctly? | Information by Electrical ...

    forums.mikeholt.com/threads/sizing-a-wire-trough-correctly.112235

    Largest wire is 350kcmil. At most, one wire per terminal. Required minimum wire bending space is at least 5". However, one of the main considerations is to not have to bend the 350's into a terminal. :happyyes: Burndy BIBS350-8 is 7.68" in length. Gutter must be at least 8" in mounted height.

  5. AC Wire Size | Information by Electrical Professionals for...

    forums.mikeholt.com/threads/ac-wire-size.2583217

    This is compliant as the overload in the motor will handle any current overload. The breaker, in this case, is only for protection from ground faults and short circuits, not overloads. That's what stood out to me - I misunderstood the line about 'Normally this is too big to protect the 12 AWG wire, but the wire is protected by the air ...

  6. NEC Table 9 Alternating-Current Resistance

    forums.mikeholt.com/threads/nec-table-9-alternating-current-resistance.134193

    The n gauge wire resistance R in ohms per kilofeet (Ω/kft) is equal to 0.3048×1000000000 times the wire's resistivity ρ in ohm-meters (Ω·m) divided by 25.4 2 times the cross sectional area A n in square inches (in 2):

  7. Increase wire size for voltage drop | Information by Electrical...

    forums.mikeholt.com/threads/increase-wire-size-for-voltage-drop.90991

    The scenario: I ask about the wire size so I know what size lugs to bring to connect the wires to the XF spades. The electrician tells me he has 175 amps, he was going to use 3/0 wire, but he had to use 350 because the length was 275'. I asked him why he was upsizing the conductor because of length alone without a calculation.

  8. Neutral Conductor Sizing & 310.15(B)(7) | Information by...

    forums.mikeholt.com/threads/neutral-conductor-sizing-310-15-b-7.90620

    For individual dwelling units of one family, two-family, and multifamily dwellings conductors as listed in Table 310.15(B)(6), shall be permitted as 120/240-volt, 3-wire, single-phase service-entrance conductors, service lateral conductors, and feeder conductors that serve as the main power feeder to each dwelling unit and are installed in ...

  9. Roof Top Units : Calcs | Information by Electrical Professionals...

    forums.mikeholt.com/threads/roof-top-units-calcs.30618

    On that example Trane unit, the VA would be 208V X 23.9A = 4,971.2 VA and then multiply that X 125% OR 1.25. 4,971.2 X 1.25 = 6,214VA or 6.2KW. The fuse size would be 23.9 X 125% or 1.25 = 29.875A or rounded off a 30Amp fuse. Minimum size wire for 30A is 10AWG copper or 8AWG aluminum.

  10. Parallel feed calculation - Mike Holt's Forum

    forums.mikeholt.com/threads/parallel-feed-calculation.69560

    Separate conduits (2), then yes, 50% in each*. Parallel in the same conduit, derating per 310.15 (B) (2) will play a roll. (*With non-linear loads 310.15 (B) (2) could still be an issue.) (as an example on your 600 amp main, parallel 350s in separate conduits would be 610 amps, 350s parallel in the same conduit -3 phase-4 wire would be 496 amps)

  11. Appropriate breaker and wire size for ductless mini split?

    forums.mikeholt.com/threads/appropriate-breaker-and-wire-size-for-ductless...

    I recently purchased a ductless mini split and am trying figure out the correct breaker and wire size. Currently I have a 220v, 30 amp breaker with 10 AWG Romex. The electrical characteristics for my LG ductless mini split are as follows: MOP 35 amps MCA 23 amps Cooling rated amps 17.55 Heating rated amps 17.55 Compressor 17.3 amps Fan 0.25 amps