Search results
Results From The WOW.Com Content Network
Such an arc can have a relatively high impedance (compared to the normal operating levels of the system) and can be difficult to detect by simple overcurrent protection. For example, an arc of several hundred amperes on a circuit normally carrying a thousand amperes may not trip overcurrent circuit breakers but can do enormous damage to bus ...
Such devices may be found in the form of either a circuit breaker, known as an earth-leakage circuit breaker (ELCB), or built into a socket (aka receptacle). Voltage-operated ELCBs can still be found in the wild, though these largely fell out of favour after the invention of the current-sensing based RCD (aka GFCI) technology.
Given "Free trip" mechanisms, I don't think you can assure that the handle tie will actually trip the "other" pole. I know I wouldn't want anything other than a true two-pole, common-trip breaker. Atlant 19:38, 17 Dec 2004 (UTC) Yes, I like that much better. Of course you can have two-pole breakers on a 120/208V panelboard, or I suppose on a ...
A shunt-trip unit appears similar to a normal breaker and the moving actuators are ganged to a normal breaker mechanism to operate together in a similar way, but the shunt trip is a solenoid intended to be operated by an external constant-voltage signal, rather than a current, commonly the local mains voltage or DC. These are often used to cut ...
A residual-current device (RCD), residual-current circuit breaker (RCCB) or ground fault circuit interrupter (GFCI) [a] is an electrical safety device, more specifically a form of Earth-leakage protection device, that interrupts an electrical circuit when the current passing through a conductor is not equal and opposite in both directions, therefore indicating leakage current to ground or ...
Oil-filled breakers contain some volume of mineral oil. A minimum-oil breaker may contain on the order of hundreds of litres of oil at transmission voltages; a dead-tank bulk oil-filled circuit breaker may contain tens of thousands of litres of oil. If this is discharged from the circuit breaker during a failure, it will be a fire hazard.
This device, which can be a circuit breaker or the first outlet on a circuit, is designed to detect hazardous electrical arcing in the branch circuit wiring as well as in cords and plugs. An AFCI device is designed to trip quickly when it detects potentially dangerous arcing that could start a fire, but not trip with harmless arcing as part of ...
At two multiples of the rated current, the recloser's rapid trip curve can cause a trip (off circuit) in as little as 1.5 cycles (or 30 milliseconds). During those 1.5 cycles, other separate circuits can see voltage dips or blinks until the affected circuit opens to stop the fault current.